Specifications, Components and
Options |
Engine Specifications |
Generator Specifications |
- Manufacturer: John Deere
- Model: 4045T
- Cylinders: 4
- Displacement: 4.5 Litres (279 cu.in)
- Bore: 106 mm (4.19 in.)
- Stroke: 127 mm (5.00 in.)
- Compression ratio: 17.6:1
- Intake air: Turbocharged
- Complete engine
specifications
|
- Manufacturer: Newage Stamford
- Model: UCI224F
- 12 lead, reconnectable, single bearing
- Rated:
- 60 kW @ 105 degree C @ 208 or 480 V at 0.8 PF
- 52.5 kW @ 125 degree C @ 120/240 V single phase @ 1.0 PF
- Brushless, solid state +/- 1-1/2% voltage regulation
|
Electrical Distribution |
|
- Linking board for simple reconnection of generator*
- Three pole fusible disconnect*
- Two Hubbel 100A pin and sleeve outlets*
- Six 230 V, 30 A Twist-lock three phase receptacles*
- CEMA 1 enclosure, CSA approved*
- Rear door constructed for cable access with door closed
*
Typical distribution components. Others by request
Metering and Controls The standard metering package
includes a saddle mounted, CSA approved instrument panel. Generator output
metering includes AC voltmeter, frequency meter, ammeter and phase selector
switch. The AC meters are fuse protected. Engine monitoring includes DC volts,
hour meter, oil pressure and coolant temperature. Standard safety shutdowns are
provides for low oil pressure and high coolant temperature. |
Fuel Tank |
- Base fuel tank with 140 Imp. Gallons (636 litres) fuel
capacity
Enclosure Sound attenuated, weather resistant, 12 ga.
sheet metal walls, 11 ga. roof. Four doors (access both sides). Rear door
access to electrical distribution equipment. Powder coat finish,
inside and outside of enclosure. Full containment to prevent external spillage.
Single point lifting.
Other Features
- Fully load tested
- Unit is serviced including oil, antifreeze and cooling system
additives
Options
- Long Run Oil System
package
- Tandem axle trailer option
- Sight level gauges for oil and coolant level
- Manual throttle control with regulator cutout switch
- Various electrical distribution options available
- A separate option listing is available
|
Generator Set Features |
Warranty |
- Standard 60 Hz. ratings and voltages with 12 lead
reconnectable brushless generator
- 75 kVA, 60 kWe @ 120/208 V, 3 phase, 0.8 P.F, 105 degrees C
temperature rise x resistance
- 75 kVA, 60 kWe @ 277/480 V, 3 phase, 0.8 P.F, 105 degrees C
temperature rise x resistance
- 52 kVA, 52 kWe @ 120/208 V, 1 phase, 1.0 P.F, 105 degrees C
temperature rise x resistance
- Optional 60 Hz. ratings and voltages
- 75 kVA, 60 kWe @ 347/600 V, 3 phase, 0.8 P.F, 105 degrees C
temperature rise x resistance
- 75 kVA, 60 kWe @ 120/208 V, 3 phase, 0.8 P.F, 105 degrees C
temperature rise x resistance
- * Oversized alternators for non-linear loads or improved motor
starting characteristics Optional 50 Hz ratings and voltages on request
|
|